from nbr_tables import get_neutral_reduction_table
from nbr_tables import get_fh_factor_table
from nbr_tables import get_conduction_table
from tools import search_in_conduction_table
def get_neutral_section(phase_section, Ib, circuit_type = 'mono', index_THD3 = 0, balanced_circuit = True, installation_method = 'B1', ft=1, fg=1):
neutral_section = 0
if circuit_type == 'mono':
neutral_section = phase_section
print('Neutral Section: ', phase_section)
elif circuit_type == 'bi':
if index_THD3 < 0.33:
neutral_section = phase_section
print('Neutral Section: ', phase_section)
pass
else:
data, thd3s = get_fh_factor_table()
fh = 0
for factor, thd3 in zip(data['Bi'],thd3s):
if index_THD3 <= float(thd3):
fh = factor
break
print('Harmonic factor selected: ', fh)
Ib1 = Ib/(ft * fg)
print('Project current modified: ', Ib * fh)
print('Current to table: ', Ib1 * fh)
neutral_section, current = search_in_conduction_table(Ib * fh, Ib1 * fh, ft, fg, '2', installation_method)
print('Neutral Section: ', neutral_section)
if fg != 1 or ft !=1:
print("Normal conditions, cable supports "+str(current)+', but with ft and fg, the real capacity is:'+ str(current*ft*fg))
elif circuit_type == 'tri':
if index_THD3 < 0.15 and balanced_circuit:
data, sections = get_neutral_reduction_table()
for section, index in zip(data, data.index):
if phase_section <= int(section):
neutral_section = sections[index]
break
if neutral_section == 'S':
neutral_section = phase_section
print('Neutral Section: ', neutral_section)
elif index_THD3 < 0.33:
neutral_section = phase_section
print('Neutral Section: ', phase_section)
pass
else:
print('THD3 over 33%')
data, thd3s = get_fh_factor_table()
fh = 0
for factor, thd3 in zip(data['Tri'],thd3s):
if index_THD3 <= float(thd3):
fh = factor
break
print('Harmonic factor selected: ', fh)
Ib1 = Ib/(ft * fg)
print('Project current modified: ', Ib * fh)
print('Current to table: ', Ib1 * fh)
neutral_section, current = search_in_conduction_table(Ib * fh, Ib1 * fh, ft, fg, '3', installation_method)
print('Neutral Section: ', neutral_section)
if fg != 1 or ft !=1:
print("Normal conditions, cable supports "+str(current)+', but with ft and fg, the real capacity is:'+ str(current*ft*fg))
else:
print('Wrog circuit type')
return -1
print('')
return neutral_section