Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

Typo in OPF formulation in README #43

Open
priyald17 opened this issue May 23, 2024 · 1 comment
Open

Typo in OPF formulation in README #43

priyald17 opened this issue May 23, 2024 · 1 comment

Comments

@priyald17
Copy link

Equation (5) currently contains the term $-\mathbf{Y_i}^s|V_i|^2$.

However, I believe this should be $-(\mathbf{Y_i}^s)^*|V_i|^2$ -- that is, the shunt admittance should be conjugated.

@ccoffrin
Copy link
Member

That's right, good catch. The software is correct but this documentation is not.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
None yet
Projects
None yet
Development

No branches or pull requests

2 participants