Register | R/W | Description | Resolution | Unit | Default |
---|---|---|---|---|---|
1000 | RW | Override the current load balancer limit (applied directly) | 0.001 | A | 16 A |
1001 | R | The current limit decided by the load balancer | 0.001 | A | |
1002 | R | The current load balancer state | |||
1010 | RW | The maximum charger current of the charger | 0.001 | A | 16 A |
1011 | RW | Number of phases | 3 | ||
1012 | RW | Alarm limit current | 0.001 | A | 24 A |
1013 | RW | Alarm limit wait time | 1 | second | 1 s |
1014 | RW | Alarm limit current change amount | 0.001 | A | 12.5A |
1015 | RW | Upper limit current | 0.001 | A | 22 A |
1016 | RW | Upper limit wait time | 1 | second | 5 s |
1017 | RW | Upper limit current change amount | 0.001 | A | 1 A |
1018 | RW | Lower limit current | 0.001 | A | 19 A |
1019 | RW | Lower limit wait time | 1 | second | 1 s |
1020 | RW | Lower limit current change amount | 0.001 | A | 1 A |
1021 | RW | Fallback limit | 0.001 | A | 0 A |
1022 | RW | Fallback limit time | 1 | second | 30 s |
1090 | W | Change the modbus server address | 10 | ||
1091 | W | Save and apply configuration (write 1) | |||
1092 | W | Restore defaults (write 1) |
The defaults are bases on an 11 kW charger on an 3 phase 25 A grid connection.
State | Description | LED Indication |
---|---|---|
0 | Normal | ._______ (1 pulse per second) |
1 | Lower limit | ._._____ (2 pulses per second) |
2 | Upper limit | ._._.___ (3 pulses per second) |
3 | Alarm limit | ._._._._ (4 pulses per second) |
4 | Fallback/Error | ----____ (0.5 sec on, 0.5 sec off) |
diagslave -m rtu -b 9600 -p none /dev/ttyUSB0 modpoll -a 1 -0 -r 1000 -t 4 -1 -b 9600 -p none /dev/ttyACM1
Schematic and PCB are available on https://oshwlab.com/timstegeman/p1_modbus_loadbalancer